Micron-gauge vacuum evacuation & decay test procedure (HVAC Laboratory)
confidence: medium
Source: HVAC Laboratory (practitioner HVAC guide). Credibility: Medium (authoritative trade technique; not peer-reviewed).
Key points
- Target: pull to 500 µm (~0.067 kPa) or lower; evacuate deep first, then admit refrigerant.
- Pump: two-stage rotary-vane mandatory (single-stage can’t beat 1000 µm), 4–8 CFM; healthy system <2000 µm in 2–3 min.
- Decay test: isolate, watch 10 min — pass <200 µm rise, fail >500 µm; gauge mounted at the vessel.
- Non-condensables: nitrogen sweep 2–3× before evacuation; pump boils off residual moisture over 30–60 min.